Adsorptive Media for Arsenic and Other Inorganic Contaminants
Many small groundwater systems treat for arsenic, and sometimes fluoride or other inorganics, with adsorptive media: a pressure vessel filled with granular media that holds the contaminant on its surface. The equipment is simple, and the chemistry is what decides whether it works. This guide explains the chemistry an operator needs, how the vessels are run, and what the monitoring must catch.
Why Arsenic, and the Standard
Arsenic occurs naturally in many aquifers. The federal maximum contaminant level (MCL) for arsenic is 0.010 mg/L (10 µg/L). It was lowered from 0.05 mg/L by a 2001 rule, with compliance required from January 2006 (40 CFR 141.62(b)). Compliance for most systems is based on a running annual average of quarterly samples at each entry point, once a system is on increased monitoring. Your monitorin