Every new main, every repaired break, every reconditioned tank and every well returned to service is a chance to push contamination into a system that customers drink from. The AWWA disinfection standards (C651 for mains, C652 for storage, C654 for wells) turn that risk into a repeatable procedure: a defined chlorine dose, a defined contact time, a flush, and a bacteriological test that must pass. This guide teaches each method, the sampling rules, and the hypochlorite math that tells you how much product to put in the bucket.
The idea behind all three standards
Chlorine at high concentration for a set time kills organisms that came in on pipe, tools, trench water or the well casing. Two facts organise everything below:
- Concentration times time is what disinfects, so high dose and short contact (slug, 100 mg/L for 3 hours) trades off against lower dose and long contact (25 m