Flow Measurement and Instrument Calibration: Flumes, Weirs, Magnetic Meters and Process Analyzers

How weirs, Parshall flumes, venturi and magnetic meters turn readings into flow, with worked calculations and calibration of pH, DO, ORP and gas monitors.

A flume or weir does not measure flow. It measures water depth, and a formula turns depth into flow. A mag meter does not measure flow either; it measures voltage. If you understand what each device really senses, you can compute flow from a reading, spot why a reading is wrong, and know exactly what to check when an analyzer drifts. This guide covers weirs, Parshall and Palmer-Bowlus flumes, venturi and magnetic meters, flow monitoring in gravity sewers and force mains, and calibration of pH, DO, ORP, H2S and pressure instruments.
Primary and secondary devices
Every flow measurement system has two parts (EPA NPDES Inspection Manual, Appendix O):
  • A primary device is the thing in contact with the water that creates a known relationship to flow: weirs and flumes relate water depth (head) to flow, venturi meters relate differential pressure to flow, and electromagnetic meters re

Read the full guide