Plains & Mountain Distribution Rules by the Numbers: Pressure, Residuals, Flushing, Boil Notices and Backflow in Texas, Oklahoma, Kansas, Colorado, Montana and Nebraska

A side-by-side guide to the distribution numbers that differ across Texas, Oklahoma, Kansas, Colorado, Montana and Nebraska: minimum pressure, chlorine and chloramine residuals, dead-end flushing, the Texas boil-water notice sequence, storage-tank inspections and backflow programs, with worked compliance examples.

Take one gauge reading: 22 psi at a customer's hose bib during the evening peak. In Kansas and Nebraska that meets the 20 psi operating minimum. In Oklahoma it breaks the 25 psi floor. In Texas it is below the 35 psi normal-operating minimum, though still above the 20 psi line that starts the boil-water process. In Colorado and Montana, a design that delivers it at normal flow fails the 35 psi working-pressure criterion. Generic exam banks teach one number; your state exam tests your state's number. This guide lines up the Plains and Mountain rules for pressure, chlorine and chloramine residuals, dead-end flushing, boil-water notices, storage tanks and backflow, explains why each exists, and works the compliance calls with examples.
Why the numbers differ from state to state
The federal floor. The Surface Water Treatment Rule (40 CFR 141.72) sets the federal minimum for disinfec