Southeastern Main Installation & Repair Rules: Separation, Disinfection and Clearance Sampling by State

Side-by-side main installation and repair rules for FL, GA, AL, MS, TN, KY and LA: sewer separation and crossings, cover and materials, AWWA C651 versus Kentucky and Mississippi 50 mg/L disinfection, clearance sampling, and break response, with eight worked examples.

The same 8-inch main break gets closed out differently depending on which Southeastern state it happens in. In Florida, a main repaired with a clamp while it stays full of pressurized water needs no disinfection and no bacteriological sampling at all. Kentucky lets you keep a broken line in service without a boil water advisory only if three conditions all hold. Tennessee requires resamples at the original site, upstream and downstream when a repaired main's sample comes back positive. For new mains, Kentucky requires 50 ppm of chlorine, and Mississippi's design criteria call for 50 mg/L unless C651 is followed. That is twice C651's 25 mg/L starting dose. This guide sets the Southeast's main installation and repair rules side by side: separation from sewers, cover and materials, new-main disinfection, clearance sampling and break response. It explains why each rule exists and works the n